مبدل مدباس RTU (MODBUS RTU) به پروفیباس DP (ProfiBUS-DP) اُ دات ODOT دارای یک پورت RS485 و یک پورت پروفیباس DP مدل ODOT-DPM01 |
ODOT-DPM01: Modbus-RTU to Profibus-DP Converter
Product Feature:
♦ Supports protocol conversion between Modbus and PROFIBUS
♦ Supports RS485, RS422 and Rs232
♦ Supports Modbus master and slave, and supports RTU or ASCII
♦ Supports working environment of -40~85°C
♦ PROFIBUS-DP: Max. Input 244 bytes, Max. Output 244 bytes
♦ DPM01:1-way Modbus to PROFIBUS slave gateway, sum of input and output is 288 bytes.
♦ DPM02: (customization) 1-way Modbus-RTU to PROFIBUS slave gateway, sum of input and outputis488 bytes.
Product Details
ODOT-DPM0l gateway is a Modbus-RTU/ASCII to PROFIBUS-DP protocol converter. This product can connect Modbus device to Siemens PLC(S7-300/1200/1500/400) with PROFIBUS-DP communication interface or DCS system with DP master. It adopts aluminum alloy shell with firm design and supports DIN-rail installation. All serial signal provides built-in photoelectric isolation.
Technical Parameters
Mechanical
Shell: Aluminum alloy
Weight: 162g(ODOT-DPM01)
Dimension: 27.5*110*110mm
Working Temperature: -40〜۸۵℃
Storage Temperature: -55〜۱۲۵℃
Relative Humidity: 5~95% (no condensation)
Input Voltage: 9 〜۳۶VDC
Wiring: 3.81mm plug screw terminal
Power: Max. 100mA@24V
Modbus Serial
Port Number: 1
Serial Port: RS485/422/232, hard wiring selection
Wiring: 3.81mm plug screw terminal
ESD Protection: ±۱۶KV
Rs485 Terminal Resistance: built-in 120Ω
Data Bits: 8
Stop Bits: 1, 2
Check digit: None, even, odd
Baud Rate: 1200~115200bps
Function Code: 01/02/03/04/05/06/15/16
PROFIBUS Interface:
Protocol: Profibus-DP/VO
Module Slots: 42pcs
Communication Rate: 9.6Kbps~ 12Mbps self-adaptive
Connection Type: Db9 female connector
Isolation Protection: Electromagnetic isolation
Terminal Number: 1
Rotary Switch: PROFIBUS address 1~255
Main Technical Parameters
Function Code Support to Modbus: 01/02/03/04/05/06/15/16
Supported Protocol: PROFIBUS-DP/V0
DP Communication Rate: 9.6Kbps ~ 12Mbps self-adaptive
DP Data Zone: Max. Input 244 bytes, Max. output 244 bytes, total sum of input and output is288 bytes
DP Slave Max: 42pcs
Modbus Slave Station Mode: Supports
Modbus Master: Supports
Modbus Station Number: Max.31pcs
Modbus Baud Rate: 1200~115200bps optional
Installation: 35mm Standard Din-rail
IP Grade: IP20
Others
Certificate: EMC, CE
Warranty: 3 years
Software: Provide GSD documents / Provide debug software