مبدل کن اوپن CAN open به مدباس (MODBUS TCP) اُ دات ODOT مدل MG-CANEX |
MG-CANEX CANopen to Modbus TCP converter
Product Feature:
MG-CANEX Protocol Converter
CANopen to Modbus TCP protocol converter
MG-CANEX is a protocol converter from CANopen to Modbus TCP. The device plays as the master in the CANopen network and it could be connected to the standard CANopen slave devices. The data transmission supports PDO, SDO, and error control supports Heartbeat. It Supports synchronous and asynchronous message sending.
As a TCP server in Modbus TCP network, the device could be accessed by 5 TCP clients at the same time, and it could be connected to PLC controller and various kinds of configuration software. It could also connect optical transceiver and to realize long-distance data transmission.
Product Details
◆ The gateway comes with its own configuration software, and the parameter configuration information is downloaded to the gateway through the network port. The gateway automatically saves the latest configuration information. There is no need to load configuration after the gateway is powered off and on.
◆ Gateway is the master of CANopen on CANopen network, and can connect to the equipment of CANopen slave
◆ The gateway is Modbus Server on Modbus TCP network and supports up to 5 TCP clients access. Double Ethernet port, with switch function, support cascade.
◆ ۲KV network port isolation protection, 10M/100Mbps rate adaptive, automatic MDI/MDIX reversal.
◆ It supports address mapping mode, and realize the rapid response to TCP client request.
◆ Modbus TCP supports function code: 0 x01, 0 x02, 0 x03, 0 x04, 0 x05, 0 x06, 0 x0F, 0 x10.
◆ ۶KB large data buffer, more data transfer volume.
◆ CAN interface supports CANopen working mode.
◆ CAN interface Baud rate: 10K~1Mbps.
◆ CANopen protocol conforms to DS301 V4.02 and supports NMT master, PDO, SDO and Heartbeat.
◆ It supports one-key reset function to restore factory Settings.
◆ ۳۵mm DIN-rail installation.
◆ EMC meets EN 55022:2010 & EN55024:2010 international standards.
Technical Parameters
Please use this product within the parameters of this product to obtain better performance.
Environmental parameters
Working temperature: -40~85℃/-۲۰~۷۰℃ optional
Storage temperature: -45~125℃
Working humidity: 5%~95% ( No condensation )
The power supply parameters
Number of power ports: 1way
Input voltage range: 9~36VDC, 3KV isolation voltage
Power consumption: Max.110mA@24V
Ethernet parameters
Modbus TCP Function code: 0x01, 0x02, 0x03, 0x04, 0x05, 0x06, 0x0F, 0x10
Number of Ethernet ports: ۲PCs of RJ45, 10M, 100M adaptive rate with switch function
Network protocol: ETHERNET, ARP, IP, TCP, ICMP
Number of TCP connections: The five largest
Modbus data store:
0xxxx area(coil): 8192 Bit
۱xxxx area(Discrete input ): 8192 Bit
۳xxxx area(Input register ): 2048 Word
۴xxxx area(Hold register ): 2048 Word
CANopen parameters
CAN baud rate: 10K~1Mbps
CAN protocol: CANopen
Number of slave supported: 16 stations
PDO functions: Support TPDO, RPDO data transmission
SDO functions: Fast SDO transfers of up to 4 bytes are supported
Error control: Support the Heartbeat