ماژول دیجیتال I/O اُ دات (ODOT) مدل CN-8031 |
Description
ODOT CN-8031 Modbus TCP Adapter
CN-8031 Modbus TCP Network Adapter supports the standard Modbus TCP
Server Communication, and Ethernet supports the cascading of dual-port
switches. It supports access to 5 Modbus TCP clients simultaneously,
Modbus function code 01/02/03/04/05/06/15/16 /23, watchdog, the process data Max. sum of input and output of 8192 bytes, and extension IO module of 32pcs. Module carries with the diagnostic function and it could monitor the status of IO module in real time.
Hardware Specification
System Power:Nominal:24Vdc, Range: 9-36Vdc
Power Consumption:۵۰mA@24Vdc
Current Output:Max. 2.5A@5VDC
Isolation: System to Field Power Isolation
Field Power: Nominal:24Vdc, Range:22-28Vdc
Field Power Contact: Max. 8A
Expansion Module: 32 Slots
Wiring: Max.1.5mm²(AWG 16)
Mounting Type: 35mm DIN-Rail
Size: 115*51.5*75mm
Weight: 130g
Environment Specification
Operation Temperature: -40~85℃
Operation Humidity: 5%-95% (No Condensation)
Protection Class: IP20
Communication Specification
Protocol: Modbus-TCP
Process Data Area: Sum of input and output:8192 Byte
Diagnostic Function: Supported
Modbus Data Storage Area:
0xxxx area (Coil): 8192 Bit
۱xxxx area (Discrete input): 8192 Bit
۳xxxx area (Input register): 2048 Word
۴xxxx area (Holding register): 2048 Word
۳xxxx area (System diagnostics – state input): 105 Word
۴xxxx area (System diagnostics – control output): 1 Word
Number of TCP: 5 Clients
TCP Keepalive: YES
Modbus Watchdog: Default Enable, 30 Seconds
Function Code: 01/02/03/04/05/06/15/16/23
Network Interface: RJ45x2
Speed: 10/100Mbps, MDI/MIDX, Full-Duplex
Distance: 100m
IP Address: DIP switch set or IO-Config software set